We investigated the role of surface microstructures in two-phase microchannels on suppressing flow instabilities and enhancing heat transfer. We designed and fabricated microchannels with well-defined silicon micropillar arrays on the bottom heated microchannel wall to promote capillary flow for thin film evaporation while facilitating nucleation only from the sidewalls. Our experimental results show significantly reduced temperature and pressure drop fluctuation especially at high heat fluxes. A critical heat flux (CHF) of 969 W/cm2 was achieved with a structured surface, a 57% enhancement compared to a smooth surface. We explain the experimental trends for the CHF enhancement with a liquid wicking model. The results suggest that capillary flow can be maximized to enhance heat transfer via optimizing the microstructure geometry for the development of high performance two-phase microchannel heat sinks.
Introduction
The increasing power densities in various electronic devices including concentrated photovoltaics, power electronics, and laser diodes pose significant thermal management challenges for the electronics industry [1–3]. Two-phase microchannel heat sinks are attractive to cool advanced electronic devices because they harness the latent heat of vaporization to dissipate high heat fluxes in a compact form factor. However, minimizing flow instabilities during boiling while enhancing the critical heat flux (CHF) to maximize heat dissipation has been difficult to achieve [4–6]. These flow instabilities which can be triggered by several mechanisms including explosive bubble expansion [7], upstream compressibility [8,9], and density wave oscillation [10] can lead to large pressure drop fluctuations across the channels and temperature spikes associated with liquid dry-out. This dry-out severely limits the heat removal ability of these microchannel heat sinks and leads to device failure once reaching CHF [11].
To suppress flow instability and to enhance heat transfer, recent studies have focused on incorporating various structures in microchannels, such as inlet restrictors [12–14], artificial nucleation sites [14,15], vapor venting membranes [16–18], micropin fins [19–21], and nanowire-coated surfaces [22–24] integrated into the microchannel. However, there are challenges with several of these approaches. Inlet restrictors can significantly reduce backflow but with a pressure drop penalty for the stabilization [13]. Fabricated nucleation sites have demonstrated enhanced nucleate boiling heat transfer; however, the introduction of the cavities alone can increase the instabilities [14]. Vapor venting membranes can reduce dry-out and pressure drop oscillations by locally removing the expanding vapor; however, the operational range is limited due to the risk of membrane flooding at high pressures [17].
Micro and nanostructure-coated surfaces are attractive owing to the ability to modify surface wettability, generate capillarity, and create nucleation sites. In fact, in pool boiling, superhydrophilic micro and nanostructures have demonstrated significantly increased CHF [25–31] and biophilic patterned surfaces have shown large enhancements in heat transfer coefficients (HTCs) [32,33]. In flow boiling, silicon nanowire-coated channel surfaces have been reported to reduce temperature fluctuations [22], increase the HTC and CHF, and decrease the pressure drop across the microchannels with water as the working fluid [23,24]. The enhancement mechanism was mainly attributed to both increased wettability in delaying CHF and nucleation sites formed by the nanowire bundles to improve the HTC in the nucleate boiling regime. At high heat fluxes, however, the annular flow regime typically dominates, where film evaporation is the important heat transfer mode [4]. Thus, the role of the surface structures on the stability of the annular liquid film and on the film evaporation performance needs to be investigated. In addition, while introducing structures on the channel wall offers capillary driven liquid flow, the associated viscous resistance [34–36] from the structures, especially in the presence of shear from the vapor, can be significant. These effects are sensitive to the geometry of the structures. Therefore, the precise role of the surface structures on flow boiling needs to be studied in more detail.
In this work, we investigated superhydrophilic microstructured surfaces in microchannels for flow boiling heat transfer. These surface structures have length scales much smaller than the height of the microchannel, and thus are different from micropin fins which extend to the ceiling of the microchannel [19–21]. We fabricated and characterized microchannels with well-defined micropillar arrays on the bottom channel wall, where heat was applied. The hydrophilic micropillars were only integrated on the heated bottom surface to promote wicking and film evaporation while suppressing dry-out. The sidewalls, with tailored roughness of 1–2 μm, promoted nucleation near the bottom corners [37]. Spatially decoupling nucleation to the sidewalls and film evaporation to the bottom surface promises to achieve high heat fluxes while maintaining stable heat transfer performance. We characterized structured surface microchannel and benchmark smooth surface microchannel devices in a custom closed loop setup. In particular, we investigated flow instabilities through temporally resolved temperature and pressure drop measurements, and simultaneous visualization of the flow in the device. We also characterized the heat transfer performance (the HTC, CHF, and pressure drop), and explained the experimental trends for the CHF enhancement with an adiabatic liquid wicking model. The insights gained from this work are a first step toward guiding the design of stable, high performance surface structure enhanced two-phase microchannel heat sinks.
Methodology
In high heat flux applications, microchannel heat sinks usually operate in the annular flow regime due to the high vapor quality associated with heat dissipation in the confined space [38]. Since evaporation can be dominant in the annular flow regime, we designed the structured surfaces to enhance and sustain stable liquid film evaporation (Figs. 1(a) and 1(b)). The structures were integrated only on the bottom heated surface where the wall temperature and the heat flux are the highest, in order to suppress liquid dry-out by generating capillary flow in the presence of menisci formation (Fig. 1(c)). This capillary flow can be created both along the channel direction and from the sidewalls to the center (the dotted line regions in Figs. 1(a) and 1(b)). The sidewalls have tailored roughness of 1–2 μm to promote nucleation [37]. By nucleating on the side walls, it is less likely for dry-out to occur on the bottom surface. In contrast, for smooth-surface microchannels, dry-out typically occurs on the bottom surface due to explosive bubble growth from it.
Device Design and Fabrication.
We investigated single microchannels with typical characteristic dimensions of 10 mm in length, 500 μm in width, and 500 μm in height. We varied the micropillar geometries on the bottom surface of the microchannel with diameters of 5–10 μm, pitches of 10–40 μm, and constant heights of 25 μm. These micropillar geometries were chosen for the following reasons: (1) The micropillars are easy to fabricate in silicon (Si) using standard etching processes and the geometries can be well controlled in this range. (2) At these length scales, the capillary pressures that can be generated are a few kPa which are comparable to the typical microchannel pressure drop. This suggests that capillary effects are not small and can be used to manipulate flow behavior. (3) The surface structures are mechanically robust and will not change morphology (deform or form clusters) as the liquid evaporates. The specific micropillar geometries fabricated and tested are shown in Table 1, which allows investigation of the effect of micropillar diameter d and pitch l on heat transfer and flow characteristics during flow boiling. Specifically, we aimed to maximize the liquid propagation coefficient in micropillar arrays with a fixed aspect ratio h/d but different pitches l based on a fluid wicking model developed by Xiao et al. [39].
Device no. | Height, h (μm) | Diameter, d (μm) | Pitch, l (μm) |
---|---|---|---|
S1 | 25 | 5 | 10 |
S2 | 25 | 5 | 15 |
S3 | 25 | 10 | 30 |
S4 | 25 | 10 | 40 |
Device no. | Height, h (μm) | Diameter, d (μm) | Pitch, l (μm) |
---|---|---|---|
S1 | 25 | 5 | 10 |
S2 | 25 | 5 | 15 |
S3 | 25 | 10 | 30 |
S4 | 25 | 10 | 40 |
To emulate the heat flux from a high performance electronic device, we integrated a thin-film metal heater (8.6 mm long × 380 μm wide) directly underneath the microchannel to serve as a heat source via Joule heating (Figs. 1(a) and 2(a)). In addition to the heating element, we incorporated four thin-film resistance temperature detectors (RTDs), which are commonly used for flow boiling studies [22–24,40,41], along the length of the heater to measure the microchannel backside surface temperature at different locations. Specifically, the distances x of RTD1 through RTD4 from the inlet of the microchannel were 0 mm, 1.4 mm, 5.7 mm, and 10 mm, respectively, (Fig. 2(a)).
Standard silicon MEMS fabrication processes were used to create the microchannel test devices and are summarized in Fig. 2. The micropillars were etched in a 500 μm thick Si wafer using deep reactive ion etching (DRIE) of the channel bottom surface (Fig. 2(b)). A second 500 μm thick Si wafer was etched through using DRIE to define the channel sidewalls (Fig. 2(c)). Inlet and outlet ports were created on a Pyrex wafer by laser drilling (Fig. 2(d)). The two Si wafers were bonded together using direct Si–Si fusion bonding. A 1 μm silicon dioxide (SiO2) layer was thermally grown on the Si surface as a hydrophilic coating on the channel walls and as an electrical insulation layer on the backside. The Pyrex wafer was subsequently bonded onto the Si wafers using anodic bonding to cover the microchannel and facilitate flow visualizations (Fig. 2(e)). Finally, a layer of ∼170 nm thick platinum (Pt) was deposited on the backside of the microchannel with electron-beam evaporation and patterned by lift-off technique to serve as the heater and RTDs (Figs. 2(f), 3(b), and 3(c)). To maximize the power dissipation capability of the heater, the target heater resistance was determined by the maximum allowable heater voltage (180 V) and current (0.5 A) to prevent burnout. To achieve this target resistance of 360 Ω, we designed the thin film heater thickness and dimensions. In addition to the microstructured microchannels, we also fabricated microchannels with smooth surfaces following a similar procedure; however, a polished Si wafer (roughness < 50 nm) was used instead of the micropillar wafer in the initial step (Fig. 2(b)).
Figures 3(a) and 3(b) show the front and backside of a fabricated microchannel device. The two open chambers next to the microchannel (Figs. 3(a) and 3(d)) were incorporated to minimize heat loss via conduction and to better isolate the effect of flow boiling in the microchannel. Figure 3(c) shows a magnified view of the Pt heater and an RTD on the backside of the microchannel. Figure 3(d) shows a scanning electron micrograph (SEM) of the cross section of the microchannel (A–A plane in Fig. 3(a)) with representative micropillars. The magnified views of micropillars on the channel bottom surface and a side wall near the bottom corner are shown in the left and right inset of Fig. 3(d). The side walls have small roughness (∼1–2 μm) from the DRIE process (Fig. 2(c)).
Experiment Methodology and Measurement Uncertainty.
We developed a closed loop test rig to characterize the microchannel test devices during flow boiling (Fig. 4). The loop consists of a liquid reservoir, a pump to provide a constant flow rate, a valve for flow stabilization, preheaters to minimize subcooling, a test fixture to interface with the test device, and various sensors. Degassed and high purity water (WX0004-1, OmniSolv, McLean, VA) was used as the working fluid. Throughout the experiment, water in the liquid reservoir was heated and degassed to saturated conditions under atmospheric pressure (Twater,res = 100 °C for Pwater,res = 1 atm). The fluid from the reservoir was pumped through the loop using a peristaltic pump (7528-30, Masterflex, Gelsenkirchen, Germany) to avoid contamination of the working fluid. In order to measure the flow rate with a liquid flow meter (L-50CCM-D, Alicat Scientific, Tucson, AZ) which has a maximum working temperature of 60 °C, the degassed liquid was cooled via heat exchange with the ambient to below 60 °C as it passed through the metal tubing (the line in Fig. 4 between the liquid reservoir and the flow meter). The mass flux chosen in this study was G = 300 kg/m2 · s, which is a commonly used value in the literature [4,15–17]. In addition, this moderate mass flux allowed for high heat flux dissipation at reasonable pressure drops and pumping powers. To achieve this mass flux, the flow rate was maintained at 4.5 ml/min. We reduced the flow rate fluctuations intrinsic to the peristaltic pump by using a high pump speed (∼70 rpm) with the smallest pump tubing available (tube ID = 0.8 mm, L/S 13, Masterflex) for the pump used in the study. However, flow rate fluctuations (±0.6 ml/min) were inevitable with the peristaltic pump at these low mass fluxes. Accordingly, a metering valve (SS-SS4-VH, Swagelok, Signal Hill, CA) was used to create additional hydraulic resistance (∼8 kPa) for flow stabilization within the loop, and was kept at a fixed opening for all the testing (the structured surface test samples and the smooth surface test sample). Since the liquid was subcooled due to heat loss to the ambient before the microchannel test section, we added preheaters (FGR-030, Omega, Stamford, CT) to compensate for this heat loss. The preheaters maintained a minimum liquid subcooling (10 °C) while also avoiding boiling at the entrance of the test fixture. Thermocouples (K type, Omega) and pressure transducers (PX319-030A5V, Omega) were used to monitor the loop conditions. The microchannel test devices were placed in an Ultem test fixture that interfaces with the loop. The test fixture was placed in an inverted microscope (TE2000-U, Nikon, Tokyo, Japan) and the flow was captured using a high speed camera (Phantom v7.1, Vision Research, Wayne, NJ) at 2000 frames/s. The two-phase flow pressure at the outlet of the microchannel was approximately Pout = 1 atm since it was connected to the liquid reservoir at atmospheric pressure.
Before the experiment, the Pt heater and RTDs were annealed at 400 °C for 1 hr to avoid resistance drift. The resistance R of the heater and RTDs after annealing was approximately 275 Ω at room temperature and 340 Ω at 120 °C. All the RTDs were calibrated in an oven and a linear correlation between the resistance and temperature was observed. The average sensitivity of the temperature with the resistance of the fabricated RTDs is ΔT = 1.4ΔR. The uncertainty of the resistance measurement (∼1.4 Ω) resulted in an uncertainty of ±2 °C in the measured temperature. The microchannels were rinsed in acetone, isopropyl alcohol, and de-ionized water, and subsequently plasma cleaned in an oxygen environment (29 W at 500 mTorr for 15 min) to remove surface contamination. During the experiments, we heated the microchannel by applying a DC voltage across the thin-film heater. The microchannel heater was connected to a DC power supply (KLP 600-4-1200, Kepco, Naju, South Korea), which was controlled using a proportional integral derivative (PID) algorithm in labview to maintain a constant output power. At each constant heat flux at steady-state, the temperatures T1 to T4 measured by RTD1 to RTD4, respectively, the pressures and temperatures at the inlet and outlet of the microchannel, the flow rate, and the voltage and current across the heater were recorded for 2 min. The heat flux was then increased by an increment of approximately 20 W/cm2 to the next value. Based on our measured temperature and pressure drop, the rise time to reach the next steady-state was less than 1 min due to the small thermal mass of the test device and the small temperature rise (∼1–2 °C, see Appendix for details). In addition, we examined the measured steady state temperature for ∼5 min and no further rise was observed. Therefore the loop was left running for at least 1 min to reach steady-state before we acquired the data at this new heat flux. All the data was recorded using a data acquisition card (NI-PCI-6289, National Instruments, Austin, TX) at a sample rate of 2 Hz. The experiments were performed twice for each sample under the same experimental conditions to verify repeatability (the samples were cleaned using the methods described here prior to each experiment). The experimental results were similar (within the error bars) and the data reported in this manuscript are from the repeated experiment. Since the microchannel is a three-layer stack that is bonded together, we cannot remove the cover layer (without damaging the sample) of the microchannel to measure the contact angle on the channel walls. However, wicking was observed with the structured surface microchannels before and after the experiment, which suggests an apparent contact angle of 0 deg.
The instrument error included the resolution of the pressure transducers (±300 Pa), the data acquisition card (±1 mV) which resulted in the uncertainty of the temperature measured by the RTDs (±2 °C), the power supply (0.06 V and 0.4 mA), and the flow meter (±1 ml/min).
Data Processing.
Due to the unstable nature of flow boiling, ΔT typically does not capture the dynamic behavior, such as periodic dry-out, which can also cause severe transient overheating issues. Therefore we defined CHF as the heat flux beyond which the following criteria hold: (1) There is at least a 5 °C jump in ΔT; (2) There is constant or periodic dry-out in terms of time-resolved temperature and pressure drop measurements, and visualizations. In the case of periodic dry-out, the temperature fluctuations were larger than 20 °C, the pressure drop fluctuations were larger than 2 kPa, and the duration of dry-out was longer than half the cycle time.
Results and Discussion
In this section, we first compare the stability of the measured temperature and pressure drop, and discuss the difference between the structured surface devices and the smooth surface device. Images and videos of the bottom heated surface were used to investigate the role of surface structures in annular flow stability. We then characterized the boiling curve and pressure drop curve, and discuss the heat transfer enhancement mechanism in the CHF and HTC. Finally, we explain the different behavior among the structured surface microchannels by extension of a liquid wicking model and provide insights into the optimization of the micropillar geometries.
Temperature and Pressure Drop Fluctuations.
Typically with smooth surface microchannels, flow instability can cause temperature and pressure drop fluctuations due to the change of flow pattern and local surface dry-out [43,44]. To study the effect of surface structures on flow instabilities, we measured the temporal change in the backside surface temperature and pressure drop across the microchannels with structured surfaces and compared to the fluctuations of a smooth surface microchannel. The midpoint backside surface temperature T3 measured from RTD3 which was the highest temperature obtained compared to T1, T2, and T4 was studied for this purpose. The smooth surface and the structured surface microchannels showed similar and small fluctuations at low heat fluxes (q″ < 400 W/cm2) for the mass flux investigated (G = 300 kg/m2 · s), since the vapor quality was relatively low and dry-out of the thin liquid film was less likely to occur compared to that at higher heat fluxes. As the heat flux increased to q″ = 430 W/cm2, temperature spikes and increased pressure drop fluctuations were observed for the smooth surface microchannels (Fig. 5(a)). At the same heat flux, all the structured surface microchannels showed small temperature ( ± 5 °C) and pressure drop fluctuations (±300 Pa), and the data of one representative structured surface device (S4) is shown in Fig. 5(a). From the visualization of the flow ((the movie is available under “Supplementary Materials” tab for this paper on the ASME Digital Collection) and Fig. 5(a)), the temperature spikes of the smooth surface correspond to dry-out at the bottom microchannel surface. In contrast, flow visualization of the structured surface microchannel (Fig. 5(a) and the “Supplementary Materials” indicated a stable liquid film covering the microchannel bottom surface. This stable liquid film contributed to the stability of the temperature and the pressure drop significantly. Dry-out on the structured surface occurred less frequently with shorter durations and less dry surface area compared to the smooth surface (“Supplementary Materials”).
With further increases in heat flux, the temperature spikes observed on the smooth surface microchannel occurred more often and gradually developed to large amplitude (>20 °C) periodic dry-out (Figs. 5(b) and 5(c) at q″ = 520 W/cm2 and 615 W/cm2, respectively). In comparison, the structured surface microchannel showed stable temperature (±5 °C) and pressure drop (±300 Pa) at the same heat flux (Figs. 5(b) and 5(c)), even at CHF (±5–7 °C and ±300–600 Pa, Fig. 6).
To further investigate the role of the structures during the dry-out process, we compared visualizations of the flow on a smooth surface and on a representative structured surface (Fig. 7, q″ = 430 W/cm2, G = 300 kg/m2 s). At t = 0 s both microchannels were in the annular flow regime. At t > 0 s, the annular liquid volume started to reduce. Dry-out occurred first from the corners on the smooth surface (t = 0.002 s), and the dry surface area expanded to the center of the microchannel (0.002 s < t < 0.010 s), leaving individual liquid islands. Due to the inability to supply liquid to the surface, the smooth surface could not maintain this liquid film and thus the dry-out area expanded. The smooth surface was completely dry from t = 0.012 s to 0.022 s before the liquid built up at the inlet reflushed the channel at t = 0.024 s.
In comparison, the structured surface (S4) maintained the liquid film due to the wicking capability of the microstructures (0.002 s < t < 0.010 s), until vapor/dry islands formed first at the center instead of the sides of the channel from t = 0.012 s (Fig. 7). This suggests that there is wicking from the sides to the center where the propagation distance is the longest. This wicking sustained the liquid film (0.002 s < t < 0.010 s) and delayed dry-out (t > 0.012 s). In general, the wicking from the structures prevented dry-out from occurring (see “Supplementary Materials”). In addition, the dry patches formed at downstream locations before the upstream locations, which indicate that there is also wicking along the microchannel length. From the above observations, it is evident capillarity generated with the structures plays a significant role in stabilizing the liquid thin film and the resulting surface temperature.
Heat Transfer Performance Characterization.
We also characterized the time-averaged heat transfer performance of the structured surface microchannels. We compared the heat flux q″ calculated by Eq. (4) as a function of the time-averaged midpoint backside surface temperature rise ΔT (Eq. (2)) for the four microstructured surface devices (Table 1) and the smooth surface device investigated, as shown in Fig. 8(a) (i.e., the boiling curves). The y-axis intercept (∼50 W/cm2) at ΔT = 0 °C was mainly due to the 10 °C subcooling, which agrees well with the estimated heat flux due to subcooling q″subcooling = cpΔTsubcooling/Amc = 63 W/cm2. The low-slope in the curves at q″ below 150 W/cm2 was due to single phase heat transfer where the onset of nucleate boiling was indicated by the sudden drop in ΔT. After the onset of nucleate boiling, the temperature rise increased with the heat flux.
The arrows in the boiling curves (Fig. 8(a)) indicate the CHF. The structured surface microchannels had a clear transition at CHF, which can be seen by the sudden drop in the boiling curve slope after CHF. The time-resolved temperature and pressure drop were also very stable before and at CHF (Fig. 6). In contrast, the smooth surface microchannel had a less obvious transition to CHF, since periodic dry-out occurred much earlier on the boiling curve from q″ = 430 W/cm2, as indicated by the temperature spikes (Fig. 5). The large error bars of ΔT for the smooth surface devices at high heat fluxes were also due to the increasing temperature oscillations (Fig. 8(a)). This resulted in a higher time-averaged temperature rise under the same heat flux compared with the structured surface microchannels and thus a gradual decrease in the boiling curve slope. As the heat flux increased, flow instabilities (temperature spikes and pressure drop oscillations) developed to large amplitude periodic dry-out or constant dry-out (longer than 1 min).
The structured surface showed an enhanced CHF with a maximum value of 969 W/cm2 at a corresponding vapor quality χ of 0.29 achieved by device S4, which is a 57% enhancement compared with that of the smooth surface microchannel (615 W/cm2 at χ = 0.19). This CHF value is significant in comparison with similar studies in literature for a mass flux G of 300 kg/m2 · s. The corresponding HTCs which were obtained from Fig. 8(a) and Eq. (8) are shown in Fig. 8(b). The structured surface microchannels showed significantly enhanced HTC even at heat fluxes close to CHF. This is due to the fact that evaporation is dominant in the annular flow, and the structures facilitate a stable liquid film and the menisci increased the thin film area. The HTC of the structured surface devices were relatively constant, which indicates that dry-out was minimized by the structures and the thermal resistance remained relatively unchanged.
Pressure Drop.
The hydrodynamic characteristics of the microchannels were also studied since pumping penalties can limit implementation of the solution in flow boiling systems [4]. Figure 9 shows the measured time-averaged pressure drop as a function of heat flux q″. The pressure drops across all devices were similar, which indicates that the additional pressure drop introduced by the surface structures in this study were negligible. The maximum ΔP was 14.3 kPa for device S4 at q″ = 969 W/cm2 and G = 300 kg/m2 · s, which resulted in a negligible pumping power of Ppump = QΔP = 1 mW, where Q is the volumetric flow rate (m3/s). This implies that the structures did not cost more pumping power while they maintained the temperature stability and enhanced heat transfer. This result is attributed to the liquid–vapor interface only forming menisci within the structures when there is insufficient liquid supply (Fig. 1(c)) which is usually at the downstream section of the microchannel. In the devices tested, there was sufficient liquid supply upstream such that the majority of liquid was on top of the structures, and the structures only acted as surface roughness and did not introduce noticeable extra viscous pressure drop. In addition, wicking from the sidewalls to the center of the bottom surface as discussed in Sec. 3.1 did not contribute to the pressure drop along the microchannel direction.
Wicking Model.
where u is the velocity, dP/dx is the pressure gradient which drives the liquid flow, μ is the viscosity of the liquid, ε is the porosity of the micropillar arrays, and α−2 is the permeability that accounts for the drag introduced by porous media, A and B are constants listed in Appendix.
where the height h is fixed (h = 25 μm). The result is shown in Fig. 10, where uave is plotted as a function of l and d. The geometries of the micropillars investigated in this study are also shown in symbols in Fig. 10 (devices S1–S4).
By comparing the results in Figs. 10 and 8(a), the microstructures that led to a higher liquid wicking velocity also had a higher CHF. This positive correlation between wicking velocity and CHF is expected based on our proposed mechanism, since efficient liquid transport helped sustain the thin film evaporation and prevent dry-out. Figure 10 also indicates that the wicking velocity depends both on the capillary pressure which creates the driving pressure gradient, and the viscous resistance, which hinders effective liquid propagation. Both terms depend on the structure geometry. Specifically, the capillary pressure approximately scales with 1/l, and the viscous drag scales with 1/l2, thus as l decreases the drag force increases faster than the driving capillary pressure. This is the reason device S1 has lower wicking velocity even though it has higher capillary pressure (due to smaller spacing) compared to device S4 because the increased viscous resistance is more significant than the increase of the pressure gradient. In fact, the geometry of the structures can be further optimized to maximize the wicking capability, and hence enhance the flow stability and heat transfer.
While this wicking model explains the trends of our results, there are limitations. First, the effects of evaporation and the curved interfaces were not accounted for. A more detailed numerical model which takes these two factors into consideration can be found in Ref. [46]. In addition, this model cannot predict the liquid velocity along the channel direction due to the existence of vapor shear stress (i.e., an axially varying vapor pressure). This velocity in the axial direction is also important in determining the CHF in microchannels. A more comprehensive model which accounts for evaporation and wicking in both lateral and axial directions needs to be developed in the future to provide more detailed understanding of the role of surface structures on flow boiling.
Conclusions
We have demonstrated the design of a two-phase microchannel heat sink incorporated with micropillar arrays as a platform to study the effect of surface structures on flow boiling in microchannels. The design decouples thin film evaporation and nucleation by promoting capillary flow on the bottom heated surface while facilitating nucleation from the sidewalls. The structures reduced flow boiling instability significantly in the annular flow regime, and achieved very stable surface temperature and channel pressure drop even at high heat fluxes close to CHF. The smooth surface showed frequent temperature spikes and pressure drop fluctuations due to dry-out, which developed gradually to CHF. Visualization of the flow pattern and the dry-out process indicates that the micropillar surface can promote capillary flow and increase flow stability by maintaining a stable annular flow and high-performance thin film evaporation. This stabilized annular flow and thin film evaporation contributed to an enhanced HTC and CHF (maximum 57%) compared to a smooth surface microchannel. The pressure drop across all devices was similar, which indicates that the additional pressure drop introduced by the surface structures in this study was negligible. A liquid wicking model in the transverse direction of the channel was developed to explain the trend in the enhancement of CHF among the structured devices. Both the experimental results and the model suggest that capillary pressure can be maximized without introducing large viscous resistance when the microstructure geometry is optimized. A more comprehensive model that accounts for wicking in the microchannel axial direction will be developed in the future to aid in further understanding the role of surface structures on flow boiling. This work provides important insights into the role and promise of incorporating micropillar designs in high performance microchannel heat sinks.
Acknowledgment
This work was partially funded by the Office of Naval Research (ONR) with Dr. Mark Spector as program manager (N00014-15-1-2483), the Cooperative Agreement between the Masdar Institute of Science and Technology (Masdar Institute), Abu Dhabi, UAE and the Massachusetts Institute of Technology (MIT), Cambridge, MA,—Reference 02/MI/MI/CP/11/07633/GEN/G/00, the Battelle Memorial Institute, the Air Force Office of Scientific Research (AFOSR) and the Singapore-MIT Alliance for Research and Technology (SMART). The research was technically supported and encouraged by the Jet Propulsion Laboratory, California Institute of Technology, under a contract with the National Aeronautics and Space Administration. The authors would also like to acknowledge the MIT Microsystems Technology Lab for fabrication staff support, help, and use of equipment.
Nomenclature
- Amc =
microchannel bottom wall surface area
- cp =
specific heat of water
- d =
diameter of the micropillar
- G =
mass flux in the microchannel
- h =
height of the micropillar
- I =
input current from the power supply
- k =
curvature of the meniscus
- l =
pitch of the micropillar
- Lc =
length of the electrical connection resistance
- Lw =
wicking distance
- Lheater =
length of the heater resistance
- =
mass flow rate
- Pcap =
capillary pressure
- Pin =
microchannel inlet pressure
- Pliquid =
liquid pressure
- Ploss =
calibrated heat loss to the environment
- Pout =
microchannel outlet pressure
- Ppump =
pumping power
- Psat =
saturation pressure
- Pvapor =
vapor pressure
- Pwater,res =
pressure of the water in the reservoir
- Q =
volumetric flow rate
- q″ =
heat flux
- q″subcooling =
heat flux due to subcooling
- r =
radius of curvature
- R =
electrical resistance
- Rc =
electrical connection resistance
- Rtotal =
total heater resistance
- R2 =
coefficient of determination
- Tave =
average microchannel backside surface temperature
- Tsat =
saturation temperature
- Twater,res =
temperature of the water in the reservoir
- T1 =
temperature measured by RTD1
- T2 =
temperature measured by RTD2
- T3 =
temperature measured by RTD3
- T4 =
temperature measured by RTD4
- u =
velocity
- U =
input voltage from the power supply
- uave =
average velocity
- W =
width of the microchannel
- Wc =
width of the electrical connection resistance
- Wheater =
width of the heater resistance
- x =
distance to the inlet of the microchannel
- α−2 =
permeability
- ΔP =
pressure drop across the microchannel
- ΔR =
electrical resistance change
- ΔT =
temperature rise/temperature change
- ΔTsubcooling =
subcooling
- ε =
porosity of micropillar arrays
- θr =
receding contact angle
- μ =
viscosity
- σ =
surface tension
- χ =
vapor quality
Appendix
Time Required to Reach Steady-State
We determined that the time of at least 1 min was needed to reach the steady-state as the heat flux was incremented by ∼20 W/cm2. This was based on our experimental observation where we constantly monitored the device temperature and pressure. A typical temperature response as the heat flux was incremented is shown in Fig. 11 (Sample S2). We measured the steady-state temperature for ∼5 min and the average temperature was constant (no further rise was observed). This fast response is due to the small thermal mass of our device (1 mm thick silicon of 1 cm × 3 cm area) and a small temperature rise of ∼1–2 °C (shown in the boiling curve, Fig. 8) associated with a small increment of heat flux (∼20 W/cm2). In addition, our flow loop was optimized to have minimal influence on the rise time of the microchannel: the inlet water temperature and flow rate were kept constant, and the flow exiting the microchannel directly entered the constant pressure water reservoir (∼1 liter, 1 atm).
Temperature and Pressure Variation Along the Microchannel
Figure 12(a) shows the measured backside temperature at the inlet (T1, T2), the midpoint (T3) and the outlet (T4) of the microchannel (Sample S4, q = 618 W/cm2). The inlet temperature was close to the saturation temperature, and the midpoint temperature was the highest among the four measured temperatures. The outlet temperature was lower than the midpoint temperature. Figure 12(b) shows the inlet and outlet pressure, and the corresponding fluid saturation temperature. Since the device did not have temperature sensors on the microchannel inner wall surface, we were not able to measure the temperature at the channel wall (the solid-liquid interface). We did not estimate the wall temperature based on the backside temperature due to complex heat spreading in the substrate to the channel bottom surface and to the side walls of the microchannel.
Wicking Model
where c = πd2/4l2 is the solid fraction. We assume no slip boundary condition (u = 0) at y = 0 (bottom surface) and a shear free boundary condition at the pillar tops (du/dy = 0 at y = h = 25 μm, where h is the height of the pillars). Since we only model the wicking process in the cross-sectional plane (from the sidewalls inward), it is reasonable to neglect shear at y = h in the lateral direction, since the shear force is mainly along the channel direction due to the vapor flow.